Regulated Contaminants

In the tables below, we have shown the regulated contaminants that were detected. Chemical Sampling of our drinking water may not be required on an annual basis; therefore, information provided in this table refers back to the latest year of chemical sampling results.

Microbiological Result MCL MCLG Typical Source
COLIFORM (TCR) In the month of July, 1 sample(s) returned as positive Treatment Technique Trigger 0 Naturally present in the environment
Unregulated Contaminant Monitoring Rule (UCMR) Collection Date of HV Highest Value (HV) Range of Sampled Result(s) Unit
Lead and Copper Period 90TH Percentile: 90%
of your water utility
levels were less than
Range of Sampled
Results
(low - high)
Unit AL Sites
Over AL
Typical Source
COPPER, FREE 2025 0.135 0.018 - 0.174 ppm 1.3 0 Corrosion of household plumbing systems; Erosion of natural deposits; Leaching from wood preservatives
LEAD 2025 8 0 - 21 ppb 15 1 Corrosion of household plumbing systems; Erosion of natural deposits
Disinfection Byproducts Sample Point Period Highest
LRAA
Range Unit MCL MCLG Typical Source
TOTAL HALOACETIC ACIDS
(HAA5)
603 EAST
GREEN
2025 9 9.4 ppb 60 0 By-product of drinking water disinfection
TTHM 603 EAST
GREEN
2025 22 22.1 ppb 80 0 By-product of drinking water chlorination
Regulated Contaminants Collection Date Highest
Value
Range Unit MCL MCLG Typical Source
BARIUM 9/5/2024 0.35 0.35 ppm 2 2 Discharge of drilling wastes; Discharge from metal refineries; Erosion of natural deposits
FLUORIDE 10/15/2024 0.907 0.907 ppm 4 4 Erosion of natural deposits; Water additive which promotes strong teeth; Discharge from fertilizer and aluminum factories
NITRATE 10/15/2024 0.25 0.25 ppm 10 10 Runoff from fertilizer use; Leaching from septic tanks, sewage; Erosion of natural deposits
NITRATE-NITRITE 3/26/2020 0.35 0.35 ppm 10 10 Runoff from fertilizer use; Leaching from septic tanks, sewage; Erosion of natural deposits