BACKFLOW INSPECTION REPORT
Property Address :
Delaware County Justice Center
3100 S Tillotson Ave
City :
Muncie
State :
IN
Zip :
47302
Phone :
765-749-9461
Owner Address :
Delaware County Building
100 W Main St Rm 211
City :
Muncie
State :
IN
Zip :
47305
Phone :
765-747-7730
Domestic: 1
Backflow Inspection - Mech Room Domestic Rear
•
DEFICIENCY FOUND
Relief valve did not open. Needs a complete rebuild kit
Inspection Conclusion
•
ADDITIONAL COMMENTS
Relief valve did not open. Needs a complete rebuild kit
Manufacturer
Watts
Model
LF009M2Qt
Size
1 1/4"
Serial Number
26092
Type of backflow
Domestic
Isolation or Containment
Containment
Inspection Type
Annual
Type of Assembly
RP
Time tested
11:02am
Check Valve #1 held at (PSID)
8.0
Check Valve #1 Closed Tight or Leaked
Closed
Check Valve #2 Closed Tight or Leaked
Closed
Bypass SCV Closed Tight or Leaked
No Bypass SCV
Relief Valve Did Not Open
Yes
Inspection Results
Failed
Testing equipment calibration date
01/02/2026
Testing equipment serial no.
08171268