Date :7/8/2026
Frequency :Annual
Service Ticket No. :ST01067599
Worksite No. :1000040559
PO No. : 
BACKFLOW INSPECTION REPORT
Property Address :
Delaware County Justice Center 3100 S Tillotson Ave
City : Muncie
State : IN
Zip : 47302
Phone : 765-749-9461
Owner Address :
Delaware County Building 100 W Main St Rm 211
City : Muncie
State : IN
Zip : 47305
Phone : 765-747-7730
INSPECTION SUMMARY
Domestic: 1
DEFICIENCIES
Backflow Inspection - Mech Room Domestic Rear
• DEFICIENCY FOUND Relief valve did not open. Needs a complete rebuild kit
Inspection Conclusion
• ADDITIONAL COMMENTS Relief valve did not open. Needs a complete rebuild kit
BACKFLOW INSPECTION - Location: Mech Room Domestic Rear
Manufacturer Watts
Model LF009M2Qt
Size 1 1/4"
Serial Number 26092
Type of backflow Domestic
Isolation or Containment Containment
Inspection Type Annual
Type of Assembly RP
Time tested 11:02am
Check Valve #1 held at (PSID) 8.0
Check Valve #1 Closed Tight or Leaked Closed
Check Valve #2 Closed Tight or Leaked Closed
Bypass SCV Closed Tight or Leaked No Bypass SCV
Relief Valve Did Not Open Yes
Inspection Results Failed
Testing equipment calibration date 01/02/2026
Testing equipment serial no. 08171268