ALARM SYSTEM INSPECTION
Property Address
:
Delaware County Justice Center
:
3100 S Tillotson Ave
City
:
Muncie
State
:
IN
Zip
:
47302
Phone
:
765-749-9461
Owner Address
:
Delaware County Building
:
100 W Main St Rm 211
City
:
Muncie
State
:
IN
Zip
:
47305
Phone
:
765-747-7730
Room C119 Hall by Kitchen
Koorsen Fire and Security performed the Annual test and inspection of a Siemens fire alarm system. Technicians tested the devices below that report back to the fire alarm control unit:
Smoke Detector:
240
Duct Detector:
8
Manual Pull Station:
25
Key Switch / Remote LED:
6
Supervisory:
2
Tamper Switch:
5
Horn / Strobe:
198
Waterflow Switch:
7
Heat Detector:
4
Strobe:
89
Standard NAC:
7
Alarm Signal:
Not Applicable
Alarm Restoral:
Not Applicable
Trouble Signal:
Not Applicable
Trouble Restoral:
Not Applicable
Supervisory Signal:
Not Applicable
Supervisory Restoral:
Not Applicable
Panel was not in a normal state upon arrival and was not in a normal state upon departure of Koorsen personnel.
FACU Battery Test
•
DEFICIENCY FOUND Batteries tested too low, need to be replaced
Panel Condition
•
DEFICIENCY FOUND Panel shows ground fault trouble
Duct Detector - RTU 1
•
DEFICIENCY FOUND 2nd Fl Mech Room duct functioned during testing, but shut down AHU until it was removed from the loop. Device needs to be replaced