Service Ticket No. : ST01067599
Inspection Conclusion
• ADDITIONAL COMMENTS
2nd Fl Mech Room duct functioned during testing, but shut down AHU until it was removed from the loop. Device needs to be replaced.
Panel shows ground fault trouble.
FACP batteries need to be replaced.
Was sensitivity performed during this visit? If it was performed, list the method of testing:
X No
Using panel data
Using a manufacture device
Using TruTest/Gemini device
| Monitoring Company: | Local |
| Operator: | N/A |
| Time Placed On Test: | 1:16 pm |
| Panel Code: | N/A |
| Circuit Class: | B |
| Panel Make: | Siemens |
| Panel Model: | FCM2041-U3 |
| Last Service Date: | / |
| Primary Normal Volts | 120 |
| Control Panel (FACU) Amps | 2 |
| Over Current Type | Circuit Breaker |
| Over Current Amps | 20 |
| Breaker Panel Location | Circuit court 4 electrical room |
| Breaker # | 16 |
Control Panel (FACU)
| Specify type of inspection | Visual & Functional Inspection |
Interface Equipment
| Specify type of inspection | Visual and Functional Inspection |
| Equipment Type | Elevator Recall/HVAC Shutdown |
Lamps / Led
| Specify type of inspection | Visual and Functional Inspection |