Service Ticket No. : ST01067599
Deficiencies
Inspection Conclusion
• ADDITIONAL COMMENTS

2nd Fl Mech Room duct functioned during testing, but shut down AHU until it was removed from the loop. Device needs to be replaced.

Panel shows ground fault trouble.

FACP batteries need to be replaced.

System Details
Was sensitivity performed during this visit? If it was performed, list the method of testing:
X No
Using panel data
Using a manufacture device
Using TruTest/Gemini device
Monitoring Company: Local
Operator: N/A
Time Placed On Test: 1:16 pm
Panel Code: N/A
Circuit Class: B
Panel Make: Siemens
Panel Model: FCM2041-U3
Last Service Date: /
System Power Supply
Primary Normal Volts 120
Control Panel (FACU) Amps 2
Over Current Type Circuit Breaker
Over Current Amps 20
Breaker Panel Location Circuit court 4 electrical room
Breaker # 16
System Test and Inspections
Control Panel (FACU)
Specify type of inspection Visual & Functional Inspection
Interface Equipment
Specify type of inspection Visual and Functional Inspection
Equipment Type Elevator Recall/HVAC Shutdown
Lamps / Led
Specify type of inspection Visual and Functional Inspection