- 9.Low-voltage power circuit breakers.
- 10.Protective relays, meters and current transformers.
- 11.Low- and medium-voltage switchgear.
- 12.Liquid-filled transformers.
- 13.Cast-resin transformers.
- 14.Wire or cable that is suitable for wet locations and whose ends have not been exposed to water.
- 15.Wire or cable, not containing fillers, that is suitable for wet locations and whose ends have not been exposed to water.
- 16.Luminaires that are listed as submersible.
- 17.Motors.
- 18.Electronic control, signaling and communication equipment.
604.3.2 Abatement of electrical hazards associated with fire exposure. The provisions of this section shall govern the repair and replacement of electrical systems and equipment that have been exposed to fire.
604.3.2.1 Electrical equipment. Electrical switches, receptacles and fixtures, including furnace, water heating, security system and power distribution circuits, that have been exposed to fire, shall be replaced in accordance with the provisions of the International Building Code.
Exception: Electrical switches, receptacles and fixtures that shall be allowed to be repaired where an inspection report from the equipment manufacturer or approved manufacturer’s representative indicates that the equipment has not sustained damage that requires replacement.
SECTION 605
ELECTRICAL EQUIPMENT
605.1 Installation. Electrical equipment, wiring and appliances shall be properly installed and maintained in a safe and approved manner.
605.2 Receptacles. Every habitable space in a dwelling shall contain not less than two receptacle outlets, though they need not be remote outlets. Instead, these outlets are to be either on separate walls, or if on the same wall, are to be at least twelve feet apart, measured horizontally.
Every laundry area shall contain not less than one grounding-type receptacle or a receptacle with a ground fault circuit interrupter. Every bathroom shall contain not less than one receptacle. Any new bathroom receptacle outlet shall have ground fault circuit interrupter protection. All receptacle outlets shall have the appropriate faceplate cover for the location.