CHAPTER 7
FIRE SAFETY REQUIREMENTS
About this chapter: Chapter 7 establishes fire safety requirements for existing structures by providing requirements for means of egress, including path of travel, required egress width, means of egress doors and emergency escape openings, and for the maintenance of fire-resistance-rated assemblies, fire protection systems, and carbon monoxide alarm and detection systems.
SECTION 701
GENERAL
701.1 Scope.
The provisions of this chapter shall govern the minimum conditions and standards for fire safety relating to structures and exterior premises, including fire safety facilities and equipment to be provided.
701.2 Responsibility.
The owner of the premises shall provide and maintain such fire safety facilities and equipment in compliance with these requirements. A person shall not occupy as owner-occupant or permit another person to occupy any premises that do not comply with the requirements of this chapter.
SECTION 702
MEANS OF EGRESS
[BE] 702.1 General.
A safe, continuous and unobstructed path of travel shall be provided from any point in a building or structure to the public way. Means of egress shall comply with the International Fire Code.
[BE] 702.2 Aisles.
The required width of aisles in accordance with the International Fire Code shall be unobstructed.
[BE] 702.3 Locked doors.
Means of egress doors shall be readily openable from the side from which egress is to be made without the need for keys, special knowledge or effort, except where the door hardware conforms to that permitted by the International Building Code.
[BE] 702.4 Emergency escape and rescue openings.
Required emergency escape and rescue openings shall be maintained in accordance with the code in effect at the time of construction, and both of the following:
- 1. Required emergency escape and rescue openings shall be operational from the inside of the room without the use of keys or tools.
- 2. Bars, grilles, grates or similar devices are permitted to be placed over emergency escape and rescue openings provided that the minimum net clear opening size complies with the code that was in effect at the time of construction and the unit is equipped with smoke alarms installed in accordance with Section 907.2.10 of the International Building Code. Such devices shall be releasable or removable from the inside without the use of a key, tool or force greater than that which is required for normal operation of the escape and rescue opening.