TABLE 1
OAKWOOD 2018 LEAD & COPPER TESTING RESULTS
EPA Copper Action Level (ug/L) 1,350
SAMPLE NUMBER COPPER RESULTS
(ug/L)
118F2038-0927.6
218F2038-1638.2
318F2038-1838.3
418F2038-1048.6
518F2038-1354.2
618F2038-0863.3
718F2038-0272
818F2038-1794.9
918F2038-07125
1018F2038-12129
1118F2038-03136
1218F2038-19136
1318F2038-05139
1418F2038-20141
1518F2038-01173
1618F2038-11187
1718F2038-14233
1818F2038-06289
1918F2038-15545
2018F2038-04771
EPA Lead Action Level (ug/L) 15.5
SAMPLE NUMBER LEAD RESULTS
(ug/L)
118F2038-08BDL
218F2038-180.86
318F2038-030.94
418F2038-090.98
518F2038-100.98
618F2038-151.13
718F2038-121.17
818F2038-161.31
918F2038-051.37
1018F2038-171.57
1118F2038-131.59
1218F2038-041.70
1318F2038-141.81
1418F2038-012.40
1518F2038-192.53
1618F2038-062.85
1718F2038-113.76
1818F2038-203.96
1918F2038-024.19
2018F2038-074.35

BDL: Below Detectible Limits

To be in compliance with the OEPA Lead & Copper Rule, sample results must be below the set action level for lead and copper, as listed in the table above, at the 90th percentile. Oakwood’s 90th percentile is highlighted in light blue above.